• H05V2-R
  • H05V2-R
  • H05V2-R
  • H05V2-R

H05V2-R

These cables are intended for fixed installation in electrical equipment or inside or outside lighting installations under protected conditions. Suitable for surface mounting or embedding in conduits only in signal and control circuits. The maximum conductor temperature in normal use can reach 90° C. It must not come into contact with other objects above 85°C.
$0.00
Cable parameter:
TUV,CE
TUV,CE
CE
CE
  • H05V2-R
  • H05V2-R

Description

Application and Description

These cables are intended for fixed installation in electrical equipment or inside or outside lighting installations
under protected conditions. Suitable for surface mounting or embedding in conduits only in signal and control
circuits. The maximum conductor temperature in normal use can reach 90° C. It must not come into contact with
other objects above 85°C.
                                                                                                                                                                                    

Standards and Approvals

HD 21.7 S2, VDE-0281 Part 7, CEI20-20/7, CE Low Voltage Directives 73/23/EEC and 93/68/EEC, ROHS Certification
                                                                                                                                                                                    

Cable Construction

- Solid Bare Copper Stranded Conductor

- Single Core, Compliant with DIN VDE 0281-3, HD 21.3 S3 and IEC 60227-3

- PVC TI3 Insulation

- Core Color Coding Compliant with VDE-0293

- H05V-U (20, 18 & 17 GA)

- H07V-U (16 GA and above)
                                                                                                                                                                                    

Technical Features

- Operating Voltage: 300/500v (H05V-U)

- Operating Voltage: 450/750v (H07V-U)

- Test Voltage: 2000V (H05V-U)/2500V (H07V-U)

- Dynamic bending radius: 15 x Ø

- Static bending radius: 15 x Ø

- Operating temperature during application: -5º C to +90º C

- Flame retardant: IEC 60332.1

- Insulation resistance: 10 MΩ x km
                                                                                                                                                                                    

Cable parameters:

Number of cores x conductor cross-sectional area

# x mm²

Nominal insulation thickness mm

Nominal outer diameter mm

Nominal copper weight kg/km

Nominal cable weight kg/km

1 x 0.5

0.6

2.1

4.8

9

1 x 0.75

0.6

2.2

7.2

11

1 x 1

0.6

2.4

9.6

14

1 x 1.5

0.7

2.9

14.4

21

1 x 2.5

0.8

3.5

24.0

33

1 x 4

0.8

3.9

38.0

49

1 x 6

0.8

4.5

58.0

69

1 x 10

1.0

5.7

96.0

115